For a more secure, richer and more pleasurable experience on the internet, click here to download Internet Explorer 8

DSCT47
Linearised Thermocouple Input DIN Transmitter, 3Hz Bandwidth


Overview of DSCT47


Click image to zoom

Each DSCT47 thermocouple input transmitter provides a single channel of thermocouple input which is filtered, isolated, amplified, linearised, and converted to a process current output. Signal filtering is accomplished with a five-pole filter, which provides 85dB of normal-mode-rejection at 60Hz and 80dB at 50Hz.

An anti-aliasing pole is located on the field side of the isolation barrier, and the other four are on the process loop side. After the initial field-side filtering, the input signal is chopped by a proprietary chopper circuit. Isolation is provided by transformer coupling, again using a proprietary technique to suppress transmission of common mode spikes or surges.

Linearisation is achieved by creating a non-linear transfer function through the module itself. This non-linear transfer function is configured at the factory and is designed to be equal and opposite to the thermocouple non-linearity.


Features

  • Interfaces to Type J, K, T, E, R, S, B, and N Thermocouples
  • Linearises Thermocouple Signal
  • 3Hz Signal Bandwidth
  • Process Current Output
  • 1500Vrms Transformer Isolation
  • ANSI/IEEE C37.90.1 Transient Protection
  • Input and Output Protected to 240VAC Continuous
  • Up to 60V Loop Voltage
  • 160dB CMR
  • 85dB NMR at 60Hz, 80dB at 50Hz
  • ±0.10% Accuracy
  • Easily Mounts on Standard DIN Rail
  • CSA and FM Approvals Pending
  • CE Compliant
* Prices shown are per unit and exclude VAT at current rate

Associated tags: COM, DSCT47, ISA, POS, RMA, Thermocouple